Fuel Flow Meter display unit TC Series■ Main function
One and two flowmeter input correspondence is selectable, and installed various functions.- Wide input frequency range 0.0006Hz to 100kHz
- Measure and display at the same time Instantaneous flow rate, Integrated flow rate, Integration time
- Arbitrary of a multiplication flow measurement mode and Measurement condition arbitrary setting
- High-speed analog output, 1 to 100ms Setting arbitrary at update time, and the multiplication pulse output equipment
- The abundant option enables addition of the outside input and output
Model List
Fuel Flow Meter display unit MODEL TC-100B/TC-100BD
It can accommodate for a flow rate detector of all frequency input.
Input signal | Single phase pulse signal or A phase/B phase 90° phase difference signal (countercurrent revision) Two flowmeters are measured the multiplication flow quantity difference (net burn-out fuel) of the single phase pulse input. |
---|---|
Measurement item | Instantaneous / Integrated flow rate , Integration time, temperature , pressure(option) |
Item display/Figure length | Instantaneous flow rate / Integrated flow rate / Integration time Simultaneous display LED indication(6 columns) |
Flow quantity multiplication method | Manual, Flow rate setting, Time setting |
Measurement mode setting | set by Arbitrary multiplication mode, Flow rate difference measurement mode, Measurement condition |
Outside output | instantaneous analog output 0 to ±10V or 4 to ±20mA select Pulsed output select from 0.001mL / 0.01mL / 0.1mL (Time to use the detector, type 213) |
Operation switch | START / STOP / RESET / REPEAT |
Electric supply source | AC90 to 260V or DC12 to 26V |
External dimensions | 220(W)×99(H)×200(D)mm (Projection things are not included.) |
Simple Fuel Flow Meter display unit MODEL TC-7500 Handling product
It fits all models of volumetric flow rate detector, made in America’s MAX LTD.
Input signal | Single phase pulse signal or A phase/B phase 90° phase difference signal |
---|---|
Measurement item | Arbitrarily select setting from Instantaneous or Integrated flow rate/Integration time |
Item display/Figure length | select from Instantaneous flow rate / Integrated flow rate Integration time LED indication (6 columns) |
Outside output | instantaneous analog output 0 to ±10V or 4 to ±20mA select |
Operation switch | START / HOLD / STOP / RESET |
Electric supply source | AC90 to 260V or DC12 to 26V |
External dimensions | 96(W)×48(H)×106(D)mm (Projection things are not included.) |
High-performance Fuel Flow Meter display unit MODEL TC-7300 Handling product
It fits all models of volumetric flow rate detector, made in America’s MAX LTD.
Input signal | Single phase pulse signal or A phase/B phase 90° phase difference signal |
---|---|
Measurement item | Instantaneous flow rate / Integrated flow rate / Integration time |
Item display / Figure length | Instantaneous flow rate / Integrated flow rate / Integration time Choice indication(2ch) LED indication(6 columns) |
Flow quantity multiplication method | Manual, Flow rate setting, Time setting |
Outside output | instantaneous analog output 0 to ±10V or 4 to ±20mA select |
Operation switch | START / HOLD / STOP / RESET depends on the external signal |
Electric supply source | AC90 to 260V or DC12 to 26V |
External dimensions | 96(W)×96(H)×177(D)mm (Projection things are not included.) |
High-performance Fuel Flow Meter display unit MODEL TC-8003 Handling product
It fits all models of volumetric flow rate detector, made in America’s MAX LTD.
Input signal | Single phase pulse signal or A phase/B phase 90° phase difference signal |
---|---|
Measurement item | Instantaneous flow rate / Integrated flow rate / Integration time |
Item display/Figure length | Instantaneous flow rate / Integrated flow rate / Integration time Choice indication(2ch) LED indication(6 columns) |
Flow quantity multiplication method | Manual, Flow rate setting, Time setting |
Outside output | instantaneous analog output 0 to ±10V or 4 to ±20mA select |
Operation switch | START / STOP / RESET |
Electric supply source | AC90 to 260V or DC12 to 26V |
External dimensions | 102(W)×93(H)×126(D)mm (Projection things are not included.) |